On our faq's page, you can find questions about flooring underlayment and floor heating systems. Get helpful information to assist with your purchase decisions and address any concerns you may have.
The QuietWarmth Float and QuietWarmth Joist systems can be powered on right away. The QuietWarmth Tile system should remain off for 28 days to allow the thinset to fully cure.
The thermostat operates the system more efficiently with the floor sensor. For floating flooring, if you can take up some rows and install the floor sensor close to a mat, that is best. Another option is if you are able to access the subfloor from below, you can drill into the subfloor at an angle and secure the floor sensor from below close to where a heat mat is located, but you must be VERY careful not to penetrate all the way through the subfloor as you risk damaging a mat or potentially your flooring. If you have a tile floor and your grout lines are big enough, you could remove the grout and inlay the sensor in a grout line, then re-grout. If none of those are viable options, then the thermostat can be operated with the room temperature feature.
No, the circuit used must be dedicated for the thermostat only. Having other lines on the same circuit will cause nuisance tripping.
For small areas (areas less than 120 square feet) we recommend using 120V mats. If you have larger areas, it would be more efficient to use 240V mats, as you would require fewer circuits and control devices. Consult with your electrician for further guidance in determining what is best suited for your areas.
In some cases, QuietWarmth can be the primary heat source for a room. This is entirely dependent on the type of subfloor, how well insulated the room is, and percentage of the room that is covered by QuietWarmth mats. We are unable to accurately predict if QuietWarmth would be sufficient to heat your room. That would require a heat-loss calculation to be performed in your home by a qualified individual.
QuietWarmth can be used below your bathroom flooring. QuietWarmth cannot be installed on the floor of your shower, in a sauna (wet or dry), steam room, below a bathtub, etc. When installing QuietWarmth Float in a bathroom, please ensure your flooring is well sealed using a silicon caulk around the shower, bathtub, toilet flange, pedestal sink, etc. It would be best to seal the entire perimeter of the room if possible.
You can use a high quality insulating electrical tape in place of the Kapton discs.
We do not recommend using a damaged mat as this could cause a safety hazard.
QuietWarmth Float cannot be installed under tile or glue-down floors. QuietWarmth Tile can be installed under floating floors.
If you have not installed your flooring yet, it is unlikely that the mat will feel warm to the touch. The mats themselves do not have enough thermal mass to build heat. If your resistance readings are in the proper range, then the mats are working properly and you should proceed with installing your flooring.
Right out of the box, take an Ohm’s reading and compare it to the chart in the installation manual for the size and voltage of your mat. It should be between the low and high range. If you cut the mat, take another reading and compare the reading to what the chart says it should be for the NEW size of the mat. When the mats are cut, the resistance WILL go up.
QuietWarmth mats will not heat above 85°F, making it a safe option for many types of flooring. If your flooring is approved for any type of radiant heat, it is safe to install over QuietWarmth. Care needs to be taken to ensure the heat is not trapped by flat bottom furniture, area rugs, “pouf” style ottomans, mattresses, etc as this may cause damage to the mats or flooring and is not covered under warranty. Proper airflow on the top of the flooring surface is essential to ensuring excessive heat does not build.
We do not recommend using area rugs directly over the QuietWarmth mat locations, as this could lead to excessive build-up of heat and potential damage. If you are concerned about safety when stepping out of a shower or bath, we recommend using wooden slat bath mats or picking up the bath rug after your feet are dry.
No, these mats are not rated for outdoor use.
No, the QuietWarmth heat mats should not be installed underneath walls, cabinets, bathtubs, vanities or any flat-bottomed furniture. You can install the mats below furniture that has “feet” and allows for airflow between the floor surface and the bottom of the furniture.
Yes. You can connect up to 120 sf of 120V mats, or up to 240 sf of 240V mats to each thermostat or power module on their own dedicated 20A circuit.
The best place to install the floor sensor (included with the QuietWarmth Thermostats) is parallel to the long side of one of the mats, within 1” of the side of the mat. If you cannot reach the long side, then position it as close to the end of the mat as possible. The floor sensor wire should not run under or over any of the mats.
Yes, you need to connect the mats to a thermostat. For best efficiency, the thermostat should have an in-floor temperature sensor. Mats should not be direct-wired to the power source.
QuietWarmth Float– No, there is no top or bottom to the mats.
QuietWarmth Tile– Yes. The bottom of the mat has an adhesive to bond the mats to the subfloor, covered by a clear film. The bottom of the mat will look shiny because of this release film. Do not remove the film until you have the mats positioned exactly where you want them; the adhesive is very aggressive!
QuietWarmth Joist- Yes, the pale yellow side of the mat is facing the installer as you look up at the ceiling. The black bars are facing the under side of the subfloor.
No. If the thermostat or power module is not reachable by the 15’ lead wires, install a junction box in the wall where the leads can reach. Connect leads in junction box & use 12/2 Romex between junction box and the control device.
The factory-attached lead wires (wires that supply power from the thermostat to the mat) are 15 feet long.
Yes. You can connect up to 120 sf of 120V mats, or up to 240 sf of 240V mats to each thermostat or power module on their own dedicated 20A circuit.
QuietWarmth Float 2-in-1 mats have lead wires attached to both ends so they can be cut and both sections used. For the standard QuietWarmth mats, the cut off portions of the mat cannot be used and should be discarded.
Yes, QuietWarmth Float and QuietWarmth Tile mats can be cut between the black bars to length. They cannot be made narrower. Follow procedures outlined in the install manual to notch back the silver bus bars and insulate the ends. QuietWarmth Joist mats must be cut at the panel indicators every 12″- they cannot be cut to any length.
No, mats need to be wired in parallel (all leads for each zone must join together in the junction box).
These steps can be done in either order, but it is easier to seal the sides of the mat after the mat is stuck to the subfloor. To seal sides, fold back the top flap & gently hold back the film (do not bend) while peeling the bottom flap release liner to expose the adhesive. Press the film down firmly on the bottom flap adhesive. Then, peel off the top release liner and press the top flap down, smoothing out wrinkles and air bubbles with your hands. The top and bottom flap seals around the film and the silver bus bars, preventing moisture from the thinset from affecting the electrical circuit. Sides of the QuietWarmth Tile mat MUST be sealed. This is a crucial step!
If your subfloor is concrete, a vapor barrier is required.
QuietWarmth Float– Over any type of subfloor an underlayment is recommended, but not required. If you are using an underlayment that has an attached vapor barrier over a concrete subfloor, you need to use an additional vapor barrier below that because you have to cut into the underlayment to recess the lead wires/connections.
QuietWarmth Tile– If you are installing tile, ensure your subfloor meets standards established by the TCNA and your tile manufacturer. Over a wood subfloor, you may need to install a tile backer prior to installation of the QuietWarmth mats. Over a concrete subfloor with any type of flooring, you need to install a liquid applied vapor barrier anti-fracture membrane.
These recommendations are necessary for other types of radiant heat systems on the market. Hydronic radiant heat systems and wire/cable-type heat mats will exceed temperatures deemed safe for the flooring, creating hot spots that can damage the flooring. These types of systems require encapsulation in a cementitious compound (such as self-leveler) to distribute and disperse the heat more evenly. QuietWarmth mats are a conductive ink film that gently and evenly disperses heat, and are self-limiting at 85° F, ensuring they will not create hot spots that will harm your flooring. For this reason, if your flooring is approved for any type of radiant heat, you can safely install QuietWarmth mats directly below your flooring.
The type of mats you need is dependent on the type of flooring you are using.
QuietWarmth Joist– retrofit, install under the subfloor between the joists. Can be installed under existing floors including carpet, but you must have access from below. Note your joists must be spaced 16” on-center for
QuietWarmth Float– install under floating flooring, provided it is a minimum of 4mm thick
QuietWarmth Tile– designed for tile or glue-down flooring, provided it is a minimum of 4mm thick
Ensure the flooring you are using is “Radiant Heat Approved”. This information can often be found in the product specifications or the installation instructions.